Convert a DeST model to EnergyPlus model

Usage

to_idf(dest, ver = "latest", copy = TRUE, verbose = FALSE, options = "objects")

Arguments

dest

A [string or DBIConnection] path to a DeST model file or a DBIConnection object.

ver

[string] A character string specifying the EnergyPlus version. It can be "latest", which is the default, to indicate using the latest EnergyPlus version supported by the {eplusr} package. Objects are generated using the project's EnergyPlus 9.0.1 baseline. Earlier targets are not maintained. Effective moisture raises the generation baseline to 9.1. Effective detailed N2 source angle tables require 9.2. Targets must support all effective features. Higher targets are produced with eplusr::transition(), not separate object writers. Physical HVAC requires the generation version's local ExpandObjects; target and intermediate IDDs are resolved by eplusr for transition. The generation/target versions are recorded in the conversion audit. Geometry compatibility has been validated against EnergyPlus 23.1; other versions currently reuse that profile with an explicit warning.

copy

[logical] Whether to copy the input DeST database to a temporary SQLite database. Note that if FALSE, the input database will be modified during the conversion. Default is TRUE.

verbose

[logical] Whether to show verbose messages. Default is FALSE.

options

[string or destep_options] Conversion configuration. Use "objects" (default) or destep_opts() to configure source inputs, time tables and HVAC representation.

Value

[eplusr::Idf] The converted EnergyPlus model. The conversion attribute and Version comments record the selected options, resolved HVAC representation, source component record counts, and necessary EMS programs. Its window_bindings table records the window, side, source surface, host enclosure/surface and original/restored ownership and type for each restored face. Restoration is also recorded in saved IDF comments. Its windows table records the type K/SC, row K, effective glass resistance, face blackness, chosen target representation and unresolved properties for each window. Supported positive-type two-layer windows use equivalent ordinary glazing with SC-derived source angle solar/grey-visible tables and ordered emissivities. Visible reflectance uses the recovered optical stack as a grey symmetric equivalent. Saved visible fields are audit metadata on this verified source branch; they do not control qualification. Other windows retain the nominal SimpleGlazing approximation. Angular interpolation and target diffuse integration remain approximations; native absorption node placement and glass heat capacity are not reproduced. Conversion does not run an optical preparation simulation. Its solar list records saved mode bindings/weights, unresolved references and raw receiver metadata. Saved source surface-family weights are audit information, not applied target distributions. EnergyPlus retains its own indoor solar and radiant-gain allocation. These assumptions also appear in saved IDF comments and do not establish whole-building equivalence. Its simulation$response records the actual target zone timestep and the verified native hourly-response/reporting boundary. Native hourly control loads and target system-step or averaged hourly loads need not share their peak value or hour. These notes do not alter target solver settings, shift the time axis or fit output loads.

Details

Outdoor ventilation retains the source minimum ACH time table. A saved OPTION.VARIANT_VENT = 0 disables the range supplement. When the saved switch is absent, conversion retains its legacy documented outdoor-temperature-band rule and warns about the assumed enabled setting. The ventilation attribute records this selection. A room group with IS_AC_ROOM = 0 retains minimum ventilation only; unused maximum and temperature-range references are not consumed. In the default outdoor-band rule, the AC availability time table does not gate the range increment. Explicit target prediction uses that schedule in its own-state selection and supports intermediate flow. The rule preserves the remaining range inputs but does not reproduce DeST's internal ventilation control algorithm. See destep_opts() for standalone target-state controls, their version requirements and approximations; none consumes source simulation results.

Window-side surfaces stored with OF_ROOM = -1 are restored from the same side of their explicit WINDOW.OF_ENCLOSURE host. Restoration requires unique references, an existing room/outdoor/ground owner and no conflicting binding on the other side. Ambiguous or incomplete relationships stop conversion. Only OF_ROOM and TYPE are restored; geometry and thermal properties are retained. The default copy = TRUE leaves the input database unchanged. A destep_restored_window_bindings warning carries the affected records in its bindings field. This restores redundant input relationships, not missing geometry or DeST solver behavior.

Storey multipliers are mapped to ZoneGroup independently of source surface boundaries. Outdoor, ground and interzone relationships are retained. Interzone pairs with unequal multipliers produce a warning and are listed in conversion$surface_boundaries: weighted outputs must not be interpreted as a physically balanced whole-building model. Successful conversion does not establish DeST thermal equivalence. Missing enclosure-side or middle-plane references produce a destep_invalid_surface_references error whose references table identifies the source enclosure, field and saved reference.

Conversion scope

Source inputs are mapped to EnergyPlus objects with documented equivalent representations where needed. Conversion does not reproduce DeST solver algorithms or guarantee matching annual loads. Unsupported selected HVAC equipment stops automatic/physical conversion with a diagnostic; it is not replaced silently by IdealLoads. See destep_opts() for supported subsets. Internal gains retain the source air and total radiant fractions. Separate surrounding-surface, floor and roof fractions are not mapped to EnergyPlus; effective sensible sources using these fractions produce a destep_unsupported_gain_distribution warning. The warning's distributions field records the affected gain types and source modes. Receiving-surface allocation and the resulting transient loads are not guaranteed equivalent. Heating setpoints above cooling setpoints are diagnosed only during hours when the effective room-type AC availability schedule is greater than zero. A destep_thermostat_conflict warning identifies the heating, cooling and availability schedule IDs, rooms and conflicting hours. The same table is retained in conversion$schedules$temperature_conflicts. Original schedules are preserved, including inactive inverted values; this diagnostic does not guarantee that EnergyPlus accepts the controls during a simulation. Terrain, solar distribution and shading-update settings retain EnergyPlus defaults. Edit the returned eplusr::Idf to change target simulation settings.

See also

to_epw(), destep_opts() for supported inputs and HVAC limitations.

Examples

if (FALSE) { # \dontrun{
to_idf(dest, "23.1", options = "objects")
opts <- destep_opts("objects", run_period = c(1L, 31L))
to_idf(dest, "23.1", options = opts)
} # }